The ZCM Range features 6 models of cost-effective air-cooled liquid chillers, with cooling capacities ranging from 7kW to 27kW. These units are equipped with a coaxial heat exchanger, R410a refrigerant, and a 400v power supply for easy plug-and-play installation.
Suitable for both indoor and outdoor use, these chillers are ideal for industrial process cooling applications and come with a variety of features including a manual water fill system, an easy-view water level indicator, and a 2, 3, or 5 bar water pump. With the aim of providing reliability, continuity of operation, high performance, and reduced maintenance costs, these chillers are perfect for industrial applications across multiple sectors.
– R410 refrigerant gas
– Rotary compressor (108 – 116 models)
– Scroll (117 – 127 models)
– Crankcase heater
– Lowara / Ebara Pump
– Thermostatic valve
– High/low pressure refrigerant gas gauges
– High/low pressure switch
– Inspectable unit panels secured by screws
– Plastic water tank with level indicator
– Manual loading system
– Thermostat probe on water tank
– Plate heat exchanger
– Y-Strainer water filter (evaporator inlet)
– Dirty strainer alarm
– Evaporator inlet/outlet temperature probes
– Water by-pass with Inlet/outlet valve
– Water differential pressure switches (117+127 models)
– Flow switch (108+116 models)
– Condenser filter
– Fans without protection grid
– Microprocessor
– Phase sequence relay
– Thermomagnetic cut-out devices on every motor
– RS485 card set-up
– IP54 protection rate
– EASY MAINTENANCE
– PLUG & PLAY
– Pump with water gauge (P2, P3, P5)
– Compressor valves
– Electronic thermostatic valve
– RS485 connection cable
– Remote terminal
– Fan speed regulation
– Fan phase cut
– Set-point compensation with external sensor
– EC fans
– Condenser coil with cataphoresis protection
– Wheels kit
– Rubber anti-vibrations kit
– Voltage 460/3/60HZ
PERFORMANCE WATER 20/15 – AMBIENT 25°C |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Cooling Capacity |
kW |
2,1 |
3,1 |
4,3 |
5,1 |
5,9 |
6,7 |
Compressors absorbed power |
kW |
0,3 |
0,6 |
0,8 |
0,9 |
1,1 |
1,3 |
EER |
5,69 |
5,03 |
5,33 |
5,39 |
5,38 |
5,04 |
|
Water flow rate |
m3/h |
0,35 |
0,54 |
0,74 |
0,87 |
1,02 |
1,14 |
PERFORMANCE
WATER 12/7 – AMBIENT 35°C |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Cooling Capacity |
kW |
1,4 |
2,2 |
3,0 |
3,5 |
4,1 |
4,6 |
Compressors absorbed power |
kW |
0,4 |
0,7 |
0,9 |
1,1 |
1,3 |
1,5 |
EER |
3,46 |
2,83 |
3,08 |
2,85 |
2,87 |
2,82 |
|
Capacity |
m3/h |
0,23 |
0,37 |
0,51 |
0,60 |
0,70 |
0,79 |
STAINLESS STEEL WATER TANK |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Capacità – Capacity |
Lt |
25 |
25 |
25 |
25 |
25 |
25 |
AXIAL FANS |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Number / Ø |
Ø |
1 / 250 |
1 / 300 |
1 / 300 |
1 / 350 |
1 / 350 |
1 / 350 |
Total nominal power |
kW |
0,04 |
0,07 |
0,07 |
0,17 |
0,17 |
0,17 |
SOUND LEVEL PRESSURE |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Noise level |
dB(A) |
47 |
47 |
47 |
47 |
47 |
47 |
NOMINAL PRESSURE PUMP |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
P3 (1) |
kPa |
335 |
315 |
276 |
251 |
251 |
229 |
Nominal power |
kW |
0,37 |
0,37 |
0,37 |
0,37 |
0,37 |
0,37 |
P5 (1) |
kPa |
573 |
549 |
506 |
478 |
475 |
451 |
Nominal power |
kW |
0,55 |
0,55 |
0,55 |
0,55 |
0,55 |
0,55 |
ELECTRICAL DATA | ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
FLI (kW) |
kW |
1,05 |
1,36 |
1,64 |
1,94 |
2,24 |
2,47 |
FLA (A) |
A |
5,65 |
7,14 |
8,54 |
9,94 |
11,04 |
12,34 |
ICF (A) |
A |
24,65 |
27,14 |
34,54 |
35,94 |
46,04 |
45,34 |
Power supply |
V/Ph/Hz |
220 / 1 / 50 |
|||||
REFRIGERANT GAS |
Type |
R134a |
R410a |
||||
PROTECTION RATE |
Type |
IP33 |
IP44 |
||||
DIMENSIONS & HYDRAULIC CONNECTIONS |
ZCM_STD |
102 |
103 |
104 |
105 |
106 |
107 |
Length |
Mm |
638 |
638 |
638 |
638 |
638 |
638 |
Width |
Mm |
578 |
578 |
578 |
578 |
578 |
578 |
Height |
Mm |
936 |
936 |
936 |
936 |
936 |
936 |
Weight |
Kg |
63 |
95 |
97 |
100 |
105 |
105 |
Hydraulic connection size (ø) |
Inch |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |
1/2 |